Please use this identifier to cite or link to this item: http://repository.kln.ac.lk/handle/123456789/25971
Title: Power Factor Improvement of Industrial Loads using a Capacitor Bank and a Solar PV System
Authors: Kalhari, Madhushika
Bandara, Hasitha Eranda
Ediriweera, Sampath
Keywords: Capacitor Bank, Power Factor Improvement, Reactive power, Solar Photovoltaic System, Voltage Source Converter
Issue Date: 2022
Publisher: Faculty of Computing and Technology, University of Kelaniya Sri Lanka
Citation: Kalhari Madhushika; Bandara Hasitha Eranda; Ediriweera Sampath (2022), Power Factor Improvement of Industrial Loads using a Capacitor Bank and a Solar PV System, 7th International Conference on Advances in Technology and Computing (ICATC 2022), Faculty of Computing and Technology, University of Kelaniya Sri Lanka. Page 6-11.
Abstract: A significant portion of the cost of manufacturing in the industry is related to electrical power. An electrical system with a low power factor is typically less effective and may also be less profitable for end users and system operators. Therefore, power factor correction is essential for effective system performance and for lowering the cost of electricity. This paper presents a study on the technical and financial benefits of power factor improvement, which is supported by a real-world industrial load with a combination of a capacitor bank and a solar photovoltaic system. A load flow software is used to model and analyse the electrical system of the site with the dynamic loads. The capacitor bank’s connected duration is calculated by keeping track of the power factor, active power, and reactive power values during the day. The capacitor bank is sized to meet the reactive power needed at night. By examining the 24-hour solar irradiance data at the location, the solar system is designed to meet the peak active power consumption of the site. The voltage source converter coupled to the solar system is adjusted to produce the reactive power required to maintain the power factor during the day. The findings demonstrate that the suggested 40 kvar capacitor bank and 553 kW solar system successfully increase power factor by 39%. A simple payback period for the suggested system is six years, and it also results in monthly savings of 905806 LKR.
URI: http://repository.kln.ac.lk/handle/123456789/25971
Appears in Collections:ICATC 2022

Files in This Item:
File Description SizeFormat 
ICATC 2022 2.pdf414.61 kBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.